Low Voltage Back
 

 

 

 

 
 
Home  >> Products >> Low Voltage >> RCD/RCCB/RCBO & so on >> BY2 Surge protective device
 

 

 

 
1. Usage and application scope
 
BY2 series surge protective device (protector in short) is applied in A.C 50/60 Hz , ≤380V in the following electric power system , such as TT , IT ,TN-S , TN-C and TN-C-S, applied in the equipotential connection of the joint of LPZ0A and LPZ1 or LPZ0B and LPZ1, which protects the electric net shocked by the thunder or surge over voltage. This protector also can be connected with voltage limitation type SPD to combine "3+1", used in the TT system. And it's not applied in the system overdue short circuit current over rated breaking continuous value.

2. Model and meaning
 
 
3. Technical Parameters
 
Item
BY2-30/2.5
BY2-30/4.0
BY2-60/2.5
BY2-60/4.0
Maxi continuous operating voltage Uc~
385V AC
385V AC
385V AC
385V AC
Impact voltage Uf
> 1.0kV
> 1.5kV
> 1.0kV
> 1.5kV
Test grade
I
I
I
I
Insulation resistance Risol
>5M
>5M
>5M
>5M
Protection volatege level Up
< 2.5 kV
< 4.0 kV
< 2.5 kV
< 4.0 kV
Response time ns
< 100 ns
< 100 ns
< 100 ns
< 100 ns
Impulse current lpeak
30kA
30kA
60kA
60kA
Quantity of electric chaarge
15As
15As
30As
30As
Nominal discharge current (8/20US) In
100 kA
100 kA
200 kA
200 kA
Rating residual current Ip
4.5kA/250V
4.5kA/250V
6.0kA/250V
6.0kA/250V
Oprating voltage of protector fuse Ih
125A
125A
250A
250A
Protection level
IP20
IP20
IP20
IP20
 
4. Main Structure and Operating Principle
 
The operating principal of the protector is refer to the sketch map, the electrodes are connected to the L /N line and PE line responsively, between the electrodes there will produce the electric interval. In normal situation, the protective device is high resistance, when the over voltage brings for electric network shocked by thunder or other reasons, the protective device will rapidly conduct and release the energy by arc light .As the impulse wave through it and after disappear, the protective device will recover to high resistance and not influence the normal operating.
 
5. Installation position and application
 
1. SPD Class B, functioning as an equipotential connection in case of lightning.
2. Installed at the joint of the LPZOA or LPZOB and LPZ1 zones.
3. It is usually installed in low voltage main distribution cabinet connected to the incoming end of the buildings.
4. It adopts 35 mm DIN rail
5. The protector is linked by 10 -35 mm2 copper wire, the earth cable should choose the double color wire over 16 mm2
 

 
 

 

 

  Back